Yanggu Xinyu Electronic Technology Co., Ltd
Home>Products>Xinyu 485 Temperature and Humidity Sensor Modbus RTU
Product Groups
Firm Information
  • Transaction Level
    VIP member
  • Contact
  • Phone
    18963538740
  • Address
    Xinyu Electronic Technology Co., Ltd., Shizilou North Road, Shizilou Street, Yanggu County, Shandong Province
Contact Now
Xinyu 485 Temperature and Humidity Sensor Modbus RTU
This product is equipped with a high-precision digital probe CPU、 Composition of communication circuits. Using imported high-precision temperature and
Product details

Temperature and humidity sensor Modbus RTU intelligent temperature and humidity transmitter instructions

One Product Function Introduction:

This product is equipped with a high-precision digital probeCPUComposition of communication circuits. Adopting imported high-precision temperature and humidity probes and intelligent transmitter portsRS232perhapsRS485Output, collect temperature and humidity, and convert temperature status tomodbus RTUOutput. It can be directly connected to secondary instruments, collectors, human-machine interfaces, and computers. It has the characteristics of high accuracy, reliability and stability, long service life, and long communication distance, making it a good choice for networked centralized monitoring of temperature and humidity.

II Application areas:

Communication base stations, archives, warehouses, laboratories, factories, workshops, computer rooms, museums, archives, libraries, hospitals, hotels, residential areas, petrochemical bases, power plants, nuclear power plants, substations, agricultural research bases, health and epidemic prevention stations, environmental protection departments, vegetable greenhouses, incubation farms, etc.

III Function Introduction

1, haveRS485perhapsRS232Communication interface, two communication methods for users to choose from.

2, supportmodbus RTUagreement ; Support software: Kingview Force Control Waiting for configuration software, supporting human-machine interfaces such as Kunlun, our company provides free testing platform software and configuration software.

3, Provide technical support: provide debugging toolsVBSource code engineeringC#Source code project, Kingview instance project.

4, Can be connected simultaneously128A communication module.

5, The communication address is freely set by the user through software.

6, Installation method: wall mounted or standard35mmRail mounted installation Compact and economical.

7, Independent research and development, equipped with core technology, can be customized according to customer requirements.

8, Size:55mm*70mmperhaps55mm*90mm(Guide rail shell)

4 Technical parameters:

Working power supply

DC9V -DC30V

notes

Temperature range

-40~80

Temperature Accuracy

±0.5℃, Resolution:0.01linear measure

Humidity range

0%~100% RH

Humidity accuracy

±1% RH (10%~85%)resolving power:0.01%

Communication input port

RS485Long distance transmission(Actual testing1200m)

Default:9600, n,8,1

Communication protocol

Modbus-RtuProtocol, users can consult and customize other protocols.

static current

<10mA(Power consumption)<0.1W

Five Register Address Table:

Serial Number

name

Modbusprotocol address

10Base system)

PLCaddress

10Base system)

content

attribute

1

humidity

0

40001

Measurement value of humidity (actual value)*100)

read only

2

absolute temperature

1

40002

Temperature measurement value

(actual value*100+27315)

read only

3

Humidity (same as1

2

40003

Measurement value of humidity (actual value)*100)

read only

4

Celsius temperature

3

40004

Temperature measurement value

(actual value*100)

read only

5

Collection frequency

4

40005

0-65535cycle

read only

6

standby

5

40006

read only