Temperature and humidity sensor Modbus RTU intelligent temperature and humidity transmitter instructions
One Product Function Introduction:
This product is equipped with a high-precision digital probeCPUComposition of communication circuits. Adopting imported high-precision temperature and humidity probes and intelligent transmitter portsRS232perhapsRS485Output, collect temperature and humidity, and convert temperature status tomodbus RTUOutput. It can be directly connected to secondary instruments, collectors, human-machine interfaces, and computers. It has the characteristics of high accuracy, reliability and stability, long service life, and long communication distance, making it a good choice for networked centralized monitoring of temperature and humidity.
II Application areas:
Communication base stations, archives, warehouses, laboratories, factories, workshops, computer rooms, museums, archives, libraries, hospitals, hotels, residential areas, petrochemical bases, power plants, nuclear power plants, substations, agricultural research bases, health and epidemic prevention stations, environmental protection departments, vegetable greenhouses, incubation farms, etc.
III Function Introduction:
1, haveRS485perhapsRS232Communication interface, two communication methods for users to choose from.
2, supportmodbus RTUagreement ; Support software: Kingview Force Control Waiting for configuration software, supporting human-machine interfaces such as Kunlun, our company provides free testing platform software and configuration software.
3, Provide technical support: provide debugging toolsVBSource code engineeringC#Source code project, Kingview instance project.
4, Can be connected simultaneously128A communication module.
5, The communication address is freely set by the user through software.
6, Installation method: wall mounted or standard35mmRail mounted installation Compact and economical.
7, Independent research and development, equipped with core technology, can be customized according to customer requirements.
8, Size:55mm*70mmperhaps55mm*90mm(Guide rail shell)
4 Technical parameters:
Working power supply |
DC9V -DC30V |
notes |
Temperature range |
-40℃~80℃ |
|
Temperature Accuracy |
±0.5℃, Resolution:0.01linear measure |
|
Humidity range |
0%~100% RH |
|
Humidity accuracy |
±1% RH (10%~85%)resolving power:0.01% |
|
Communication input port |
RS485Long distance transmission(Actual testing1200m) |
Default:9600, n,8,1 |
Communication protocol |
Modbus-RtuProtocol, users can consult and customize other protocols. |
|
static current |
<10mA(Power consumption)<0.1W) |
|
Five Register Address Table:
Serial Number |
name |
Modbusprotocol address (10Base system) |
PLCaddress (10Base system) |
content |
attribute |
1 |
humidity |
0 |
40001 |
Measurement value of humidity (actual value)*100)
|
read only |
2 |
absolute temperature |
1 |
40002 |
Temperature measurement value (actual value*100+27315) |
read only |
3 |
Humidity (same as1) |
2 |
40003 |
Measurement value of humidity (actual value)*100) |
read only |
4 |
Celsius temperature |
3 |
40004 |
Temperature measurement value (actual value*100) |
read only |
5 |
Collection frequency |
4 |
40005 |
0-65535cycle |
read only |
6 |
standby |
5 |
40006 |
|
read only |