Xinkai Pu Electronics Co., Ltd
Home>Products>Single/dual control prepaid electricity meter
Single/dual control prepaid electricity meter
The new Kaipu prepaid electricity meter complies with relevant standards and requirements such as GB/T 17215.321-2008 "Level 1 and Level 2 Static AC A
Product details

Product Features

Adopting advanced measurement and control chips, it has the function of judging high-power resistive loads, which can achieve power outage under adverse loads and overload, and accurate measurement of active energy;

Using external E2PROM to store data, with a lifespan of up to 10 years, supporting power-off data storage function, ensuring safe and reliable data storage;

Support power-off and power replenishment operations;

Intelligent management: Download electricity, measure electricity consumption, and manage relay disconnection based on remaining electricity. Changing rooms for students does not affect their normal purchase and use of electricity;

Accurate control of malignant loads and overloads, with overload and malignant load identification power modules that can be independently set through software. Malignant load identification only takes 2 seconds;

Rich prompt information: LCD display, can display the current recharge power, remaining power, cumulative power consumption, purchased power, room number, overload, malicious load, and abnormal prompt information;

Intelligent flashing of work indicator light;

The communication part adopts optoelectronic isolation and lightning protection design, making communication more reliable;

The system provides real-time power, grid frequency, and other electrical parameters;

Humanized power supply and outage management;

There are two communication modes available: current loop communication and RS-485;

project
Parameter indicators
notes
Execution standards GB/T 17215.321-2008
starting current The load current is 0.4% Ib, the reference voltage is 230V, the reference frequency is 50Hz, and the power factor (cos φ) is 1 Under these conditions, the electricity meter should continuously measure electrical energy
shunt running Under the condition of 115% reference voltage (265V) Under the condition of no load current and voltage, the electricity meter should not output pulses (not measure electrical energy)
working voltage Rated voltage from 0.70 to 1.15 (165V to 265V)
Electric meter constant 3200 imp/kWh
insulation test ≥2KVAC/1MIN
power consumption Voltage line ≤ 2W (10VA) Current line ≤ 4VA
Anti lightning voltage Exchange 6KV
External dimensions 115*160*65mm
weight About 0.45kg