1、 Performance characteristics:
1. High precision measurement of three-phase AC voltage
2. Provide digital tube or LCD display, local data query
3. Programmable voltage ratio setting (LYU-DE301 cannot set ratio)
4. Supports RS-485 communication and Modbus RTU protocol
5. Support switch input, switch output, analog transmission output
6. Wide range AC/DC universal power supply: AC/DC 80V~270V
7. Multiple appearance options to meet the requirements of different cabinet electrical circuits
2、 Technical indicators:
1. Measurement accuracy: Voltage: Level 0.5
2. Signal input: Wiring method: three-phase four wire, three-phase three wire Rated voltage: AC 57.7V、AC 100V、AC 220V、AC 380V
Overload: 1.2 times (continuous), 2 times/1 second (instantaneous)
Power consumption:< 1VA/phase impedance:> 300k Ω frequency: 45-65Hz
3. Auxiliary power supply:
Scope of work: AC/DC 80V~270V Power consumption: < 4VA
4. Functional modules:
Communication interface: 1-channel RS-485 communication, Modbus RTU protocol baud rate: 2400-19200bps, default 9600bps
Switch input: supports 4-channel dry node input
Switching output: Supports 3 relay outputs, with a capacity of AC 250V/5A, DC 30V/5A
Transmission output: supports 3-channel analog output 0/4-20mA or 0-5/10V
5. Environment:
Working temperature: -10 ℃~+55 ℃ Environmental temperature:- 25℃~+70℃
Relative humidity: ≤ 93%, non corrosive gas location altitude: ≤ 2500m
6. Safety:
Insulation resistance:> 100M Ω AC withstand voltage: AC 2kV
7. Electromagnetic compatibility performance:
Electrostatic discharge: Level 4 rapid transient pulse train: Level 4 surge (impact): Level 4
8. External dimensions:
Frame size (mm) 83 × 83; 96×96; 76×76; 48×48
Hole size (mm) 76 × 76; 91×91; 67×67; 45×45