Product standards
GB/T 13850-1998 Electrical measurement transmitters for converting AC electrical quantities into analog or digital signals
Type Designation
TECHNICAL INDEX
measurement accuracy | |
Transducer |
0.5level |
INPUT | |
Connection |
Single phaseThree phase four wire, three phase three wire |
rated voltage |
AC 57.7V、AC 100V、AC 220V、AC 380V |
Rated current |
AC 1A、AC 5A |
Overload |
Voltage:1.2times(sustain),2times/1second(instantaneous) electric current:1.2times(sustain),10 times/5 seconds(instantaneous) |
power consumption |
Voltage:<1VA/each other electric current:<0.4VA/each other |
impedance |
Voltage:>300kΩ electric current:<20mΩ |
frequency |
45~65Hz |
Auxiliary power supply | |
scope of work |
AC/DC:80V~270V |
power consumption |
<5VA |
functional module | |
communication interface |
1roadRS-485Communication,Modbus-RTUagreement Baud rate:2400~19200bps, default9600bps |
Transmission output |
support3Analog output:0/4~20mAperhaps0~5/10V |
Electric pulse output |
support2-channel power pulse output Constant:5000 or20000imp/kWh(kvarh) |
environment | |
operation temperature |
-10℃~+55℃ |
storage temperature |
-25℃~+70℃ |
relative humidity |
≤93%In non corrosive gas environmentsIf special needs can be met98%) |
altitude |
≤2500m |
secure | |
insulation resistance |
>100MΩ |
ac withstand voltage |
AC 2kV |
Electromagnetic compatibility performance | |
Electrostatic Discharge |
4level |
Electric fast transient pulse train |
4level |
Surge (impact) |
4level |