This product accepts inputs from switches or proximity switches in hazardous areas, and outputs them to relays or transistors on the safety side throu
Product details

Product Introduction

Single channel, dual channel (isolated).
It has power distribution function (approximately 8V open circuit).
Contact switch, proximity switch input.
Relay or transistor output.
Positive and negative phase outputs can be set through the dip switch.

summary

This product accepts inputs from switches or proximity switches in hazardous areas, and outputs them to relays or transistors on the safety side through safety barriers. It has input status detection indicators and can be controlled in both forward and reverse directions. The product requires independent power supply, with input/output/power isolation. Can be used in NAMUR proximity switches, switches, and other field equipment that comply with DIN19234 (including intrinsically safe pressure, temperature, and liquid level switches).

safety certification
Certificate No GYB081021
Explosion proof sign [Exia] IIC (National Explosion proof Safety Supervision and Inspection Station Certification for Instruments and Meters)
Authentication parameters
terminal 8-7, 11-10
Maximum allowable voltage Um=250V
voltage Uo=10.5V
electric current Io=16mA
power Po=42mW
capacitance Co=2.4μF
inductance Lo=80mH
Wiring diagram


Single input single output wiring diagram


Dual input dual output wiring diagram

terminal number Terminal Description
Safe Zone (Green) 1 OUT1A(S-)
2 OUT1B(S+)
3 OUT2A(S-)
4 OUT2B(S+)
5 POW(+)
6 POW(-)
Dangerous Zone (Blue) 7 IN1A
8 IN1B
10 IN2A
11 IN2B


Application 1: Transistor collector output Application 2: Transistor emitter output

Structural Outline Drawing

EVT1/EVT2: Working indicator light: When the input signal is short circuited, the indicator light is green; When the input signal is disconnected, the indicator light is red.
35mm guide rail installation, please pay attention to stable and firm positioning during installation.
Please install it vertically as much as possible to facilitate heat dissipation inside the instrument.
Technical Parameter
power supply
Rated working voltage range DC 24V±10%
power consumption

Single output: ≤ 0.8W, dual output ≤ 1.2W

Dangerous side
Input Signal Type Contact switch, proximity switch (frequency ≤ 5KHZ)
Distribution voltage ≈ 8V (open circuit)
Short circuit radio wave ≈8mA
Safety side
Output signal type Relay/transistor
Relay output driving capability 125VAC/0.6A 30VDC/2A
Relay response time <5ms
Transistor output When collector output (see application 1 for wiring method): High level VCC (≤ 30V), low level ≤ 2.5V
When the emitter outputs (see application 2 for wiring method): high level VCC-2.5V, low level ≤ 0.5V
Input and output characteristics (when set to in-phase control)
On site switch closed or input circuit current>2.1mA, output relay or transistor conducting, channel green indicator light on
On site switch open circuit or input circuit current < 1.2mA, output relay or transistor non-conductive, channel red indicator light on
Input and output inverse control settings
Set by panel dial switch J5 (see accompanying manual for details)
Dielectric Strength
Local security end and non local security end 2500V,a.c; 1min
environmental condition
ambient temperature 0~50℃
ambient humidity 5% to 95% RH (non condensing)
Standard
electromagnetic compatibility Compliant with GB/T18268 Industrial Equipment Application Requirements

instrument selection

7 8 9 10
Switch input detection terminal isolation gate NHR-A35 - / - /
position specifications explanatory note

|
|
|






/

|
|
|

|
|
|
|
|
|
|
|
|
|












/

|
|
|
|
|
|
|
|
|
|

7/8 <Input>
Input I/Input II (select code from list)
code Type
X No input (limited to output II)
36 Switching quantity
9/10 <Output>
Output I/Output II (select code from list)
code type
X No output (limited to output II)
K1 Relay contact
K2 transistor
Model example: NHR-A35-36/36-K1/K1.
Switch input detection terminal isolation gate, dual input signal is switch quantity, dual output is relay contact signal.