Fangkuai Boiler Co., Ltd
Home>Products>Fuel gas water pipe hot water boiler - condensing type
Firm Information
  • Transaction Level
    VIP member
  • Contact
  • Phone
    17317613565
  • Address
    East section of Haihe Avenue, High tech Development Zone, Anyang City
Contact Now
Fuel gas water pipe hot water boiler - condensing type
Double drum longitudinally arranged fully membrane water-cooled wall D-type furnace natural circulation boiler with strong output, high thermal effici
Product details

3.jpg



Widely used

4.jpg

Full membrane water-cooled wall sealing structure

To provide production steam for food, printing and dyeing, pharmaceutical, chemical and other enterprises, to provide steam for heating other enterprises, hotels, and also to provide domestic hot water through water tank heating.

The boiler adopts a full membrane water-cooled wall structure, which has good sealing, low heat dissipation loss, and low thermal inertia, and can achieve rapid start-up and shutdown of the boiler.

5.jpg Excellent matching of combustion system ensures boiler operation status

6.jpg

9 major safety protection devices ensure safe operation

We use well-known brands of burners and gas valve groups as auxiliary equipment and components, providing a complete gas valve group and accessories including filters, pressure regulating valves, solenoid valves, etc., to ensure the safety of gas. At the same time, it can keep the boiler operating in a combustion state, achieving the dual effects of energy conservation and environmental protection.

Nine safety protection devices, including automatic flame regulation and detection, high pressure protection, gas valve group and protection system, flue gas overheating protection, power-off protection, motor phase loss and overload protection, and burner limit opening protection, ensure the safe operation of the boiler.

Performance advantages

方快燃油气水管热水锅炉结构图


Fangkuai fuel oil gas water pipe hot water boilerProvide heating and domestic water for various enterprises, institutions, and heating companies.



方快燃油气水管热水锅炉内部



Compact D-type layout structure

Small footprint, fast installation

  • Adopting a double drum vertical D-shaped layout structure

  • Full membrane wall structure micro positive pressure chamber has good combustion sealing and low heat dissipation loss

  • The boiler is a modular quick installation structure with a fast installation cycle

  • Can achieve rapid start stop of boilers





方快燃气水管锅炉生产设备





Advanced membrane wall production equipment

The qualification rate of automatic welding flaw detection is 100%


  • Boiler welds shall undergo heat treatment to relieve stress after welding in accordance with JB/T1613

  • Automated welding equipment ensures the qualification rate of non-destructive testing

方快燃油气水管热水锅炉外观




Ladder waste heat recovery improves thermal efficiency and reduces pollutants

  • Adopting the design concept of flue gas cascade waste heat recovery, a flue gas condenser is installed at the tail of the boiler body, which reduces the flue gas temperature (<100 ℃), improves boiler efficiency, and also reduces harmful components in the flue gas.

  • The condenser not only absorbs a large amount of sensible heat from the flue gas, but also absorbs a large amount of latent heat from the flue gas, making the boiler efficiency higher than that of ordinary boilers.



方快燃油气水管热水锅炉运输方便





Convenient and fast transportation, installation, and maintenance


  • This boiler is a fully assembled boiler that meets the transportation size requirements while shortening the installation cycle. At the same time, it is connected to the skeleton with bolts for easy disassembly and maintenance.

方快燃气热水锅炉防护装置

Multiple protection functions ensure safe and stable operation of the boiler


  • Time setting function: Users can set the start and stop time of the boiler according to their needs.

  • It has the functions of automatic flame adjustment and automatic flame detection.

  • Capable of displaying the temperature of boiler inlet and outlet water; Convenient for users to set the boiler's water supply temperature according to their load needs, thereby reducing operating costs.

  • Smoke over temperature protection: Equipped with a smoke monitoring device, it can automatically monitor the exhaust temperature of the boiler. When the smoke temperature exceeds the set value, the boiler will be shut down and an audible and visual alarm will be triggered.

  • Power outage protection: When the external power supply suddenly loses power, the boiler stops running. When power is restored, it must be restarted before the boiler can operate.

  • Motor phase loss and overload protection: When the fan motor experiences phase loss or overload, the thermal relay will activate, cutting off the fan power supply, shutting down the furnace, and sounding an audible and visual alarm.

方快燃油气水管锅炉智能控制



Chinese large screen control with simple operation

  • Standard PLC control system and 10 inch touch screen human-machine interface

  • Real time dynamic display of boiler operation screen and related parameters, intuitive and convenient

  • Display operating parameters such as temperature of heat medium water, vacuum degree, inlet and outlet water temperature inside the furnace

  • Fault records and operating curves are analyzed based on data for economic operation




For detailed information about Fangkuai Boiler products, please call our customer service hotline or click on the online consultation button on the right

Customer service hotline: 400-100-9030


Technical Parameter


Project model
unit
SZS10.5-1.25/130/70-Y(Q) SZS14-1.25/130/70-Y(Q) SZS17.5-1.6/130/70-Y(Q) SZS21-1.6/130/70-Y(Q) SZS24.5-1.6/130/70-Y(Q) SZS29-1.6/130/70-Y(Q)
Rated thermal power
MW
10.5 14 17.5 21 24.5 29
Rated outlet pressure
MPa
1.25
1.25 1.6 1.6 1.6 1.6
Wind turbine power
KW
37
55 75 90 90 110
Fuel diesel oil Kg/h 914.5 1245.5 1524.4 1829.3 2134.1 2540.7
heavy oil Kg/h 950.8
1267.7 1584.7 1901.6 2218.6 2641.1
natural gas Nm^3/h 1004.8 1388.3 1674.6 2009.6 2344.5 2791.1
city gas Nm^3/h 2040.8 2721.1 3401.4 4081.6 4761.9 5668.9
liquefied petroleum gas Nm^3/h 367.4 489.8 612.3 734.8 857.2 1020.5
air supplypressure
natural gas mmH2O 2000-3000 2000-3000 3000-20000 3000-20000 15000-20000 15000-20000
Urban gas mmH2O 2000-3000 2000-3000 3000-20000 3000-20000 15000-20000 15000-20000
Liquefied petroleum gas mmH2O 3000-4000 3000-4000 5000-20000 5000-20000 15000-20000 15000-20000
Transport dimensions long mm 8300 8416 9640 10120
10360 10760
wide mm 3385
3385 3830 3800 4200 4200
high mm
3800 4016 4070 4070 4332 4332
Installation size
long mm 10230 11100 12634 12755 13300 13705
wide mm 7645 7645 6213 7740 8330 8330
tall mm
5000 5205 5150 5300 5476 5476
Transport weight
T 30 31 40 43 47 50
Water inlet PN MPa 1.6
2.5 2.5

DN mm 200 200 200 250 250 250
outlet PN MPa 1.6
2.5 2.5

DN mm
200 200 200 250 250 250
Oil supply import DN mm 22 22 22 25 25 25
Oil supply outlet DN mm
22 22 22 25 25 25
Gas supply port
DN mm
According to the gas supply pressure
Manual sewage outlet PN MPa 1.6
2.5
DN mm
50
safety valve
interface DN mm 100 125 125 150 150 150
PN MPa 1.6
2.5
bleeder DN mm 125 150 150 200 200 200
Smoke exhaust interface size mm
800*500 1400*1050 1400*1050 1400*1050 1800*1050 2050*1050
general supply water temperature 130 thermal efficiency % 95-98 combustion method MPa Micro positive pressure chamber combustion
Rated inlet water temperature 70 Use power supply V/Hz 380/50 Combustion regulation method MPa Fully automatic proportional adjustment

The above parameters do not have contractual nature and should be subject to the specific terms of the contract

The fuel consumption is the value after installing the condenser; Fuel calorific value: heavy oil 9860kcal/kg, diesel 10250kcal/kg, natural gas 9140kcal/Nm3, liquefied petroleum gas 24998kcal/Nm3, city gas 4500kcal/Nm3; Due to the continuous improvement of technology, any changes will not be notified; Please request detailed parameters from Fangkuai headquarters.

Online inquiry