Product Introduction
FLOWLINE tuning fork liquid level switch SWITCH-TEK series LZ12 This universal liquid level switch adopts 1-circuit 1A relay output, which can reliably detect the liquid level of light to medium covering layer, scaling or foam polluted liquid. Typical media include sewage, diluted sodium hydroxide solution, and light oil. To achieve excellent performance, the SWITCH-TEK series LZ12 tuning fork level switch will automatically adjust according to the coverage layer and issue proactive maintenance alarms and cleaning prompts when necessary. Immersion Ryton ® Liquid level sensors are usually installed on tank walls or inside storage tanks for high or low liquid level alarms.
Technical Parameter
Installation location: Universal
Accuracy: ± 1mm (in water)
Repeatability: ± 0.5mm (in water)
Supply voltage: 12-300VDC
Power consumption: maximum 25mA
Working temperature: -40 ℃ to 80 ℃
Contact capacity: 600VA, maximum 1A
Contact type: (1) SPST relay
Contact output: normally open (NO) or normally closed (NC) optional
Maintenance alarm: NPN transistor maximum 10mA
Pressure: 10 bar at 25 ℃, with each increase in temperature
1 degree decrease of 0.113bar
Cable type: # 24 American 5-core shielded
Cable length: 10 "(3m)
Installation interface: 3/4 "NPT (3/4" G)
Installation gasket: Viton ®
Protection level: NEMA 6 (IP68)