Shanghai Ziyi Automation Instrument Co., Ltd
Home>Products>Double flange liquid level transmitter
Double flange liquid level transmitter
Double flange liquid level transmitter
Product details
ZY3051LP Double Flange Liquid Level TransmitterDetailed information:

ZY1151LPDouble flange liquid level transmitterBy combining a differential pressure transmitter with an intelligent amplification board, an intelligent remote pressure and differential pressure transmitter can be formed. When combined with a handheld device that complies with the HART protocol, it can communicate with each other for setting and monitoring

purpose

ZY3051LPDouble flange liquid level transmitterIt is a method of sensing the measured pressure through a remote transmission device installed on a pipeline or container. The pressure is transmitted to the transmitter body through a capillary filled with silicone oil (or other liquid), and then converted to 4-20mA by the delta chamber and amplification circuit board inside the transmitter body DC signal output (see schematic diagram).
ZY3051LP
differential pressure transmitterCombined with an intelligent amplification board, it can form an intelligent remote transmission pressure and differential pressure transmitter. When paired with a handheld device that complies with the HART protocol, it can communicate with each other for setting and monitoring.
In order to meet different installation requirements, this series of transmitters has multiple forms of remote transmission devices for users to choose from, and the main structure of the transmitter is the same as the differential pressure.

Remote transmissionTransmitterMainly used for measurement in the following situations

Viscous medium at high temperature
Easily crystallizable medium
Settling media with solid particles or suspended solids
Strong corrosive or highly toxic media
Can eliminate the occurrence of pressure pipe leakage and pollution of the surrounding environment; It can avoid the tedious work of frequently replenishing isolation fluid due to the instability of measurement signals when using isolation fluid.
Continuous and precise measurement of interface and density
The remote transmission device can avoid the mixing of different instantaneous media, thus enabling the measurement results to truly reflect the actual situation of process changes.
Places with high hygiene and cleanliness requirements
In the production of food, beverage, and pharmaceutical industries, not only is it required that the contact area of the transmitter with the medium meet hygiene standards, but it should also be easy to rinse to prevent cross contamination of different batches of media.

Product Features

Simulate "online operation" assessment for each transmitter to ensure stable and reliable operation under extreme environmental temperature, medium temperature, and working pressure (including positive pressure or vacuum).
Adopting a "dynamic profile" remote transmission membrane structure, the membrane will not be damaged after overload; The accuracy will not change after long-term work.
The use of a full fusion welding and rigid sealing structure filling system has eliminated the occurrence of oil leakage.
A novel capillary coupling component is designed to provide reliable protection for the capillary, making it less prone to breakage during on-site use.
A variety of remote transmission devices in terms of variety, form, and size, as well as a rich variety of filling fluids, can meet the measurement needs of various occasions.
We can provide various special needs products, including high temperature, high vacuum, fast response, and unequal long capillary (difference ≤ 4.5 meters) remote differential pressure transmitters.

Technical parameters and performance

Output signal: 4-20mA DC two-wire system (analog)
The two-wire 4-20mA DC signal is overlaid with a digital signal, and the user selects linear or square root output. (Intelligent)
Power supply: 12-45V DC (see load characteristic diagram for details)
Load characteristics:
Power supply impact:<0.005% output range/V

Load impact: When the power supply is stable, there is no load impact.
Measurement accuracy: ± 0.1% and ± 0.2% of the calibration range
(The standard precision is ± 0.2%. If you choose other precision, please indicate it when ordering and selecting.)
Range ratio: 10:1 or 100:1

Damping: It is usually adjustable between 0.1 and 16 seconds, and the time constant increases when filled with inert fluid or with a remote transmission device.
Start time:<2 seconds, no preheating required

Working environment: ambient temperature -29~93 ℃ (analog amplifier)
-29~75 ℃ (digital/smart amplifier)
-29-65 ℃ (with display header)
Environmental humidity: 0-95%
Protection feature: IP65 protection capability
Explosion proof type: Explosion proof Exd II BT4-6
Intrinsically safe Exia II CT5
Static pressure influence: Zero position error: ± 0.5% maximum range limit, calibrated by zeroing for 32MPa under pipeline pressure.
Electromagnetic radiation impact: 0.05% maximum range value, accepted radiation frequency of 27-500MHz, test field strength of 3V/m.
Indicator (%): LCD digital display accuracy ± 0.2%
Vibration effect: ± 0.05%/g when vibrating at 200Hz in any direction.
Installation position: The diaphragm is not installed vertically, which may result in a zero point error of less than 0.24KPa, but it can be corrected by adjusting the zero point.
Weight: 3.9Kg (excluding accessories)

Note: The static pressure of the remote differential pressure transmitter also depends on the specifications of the selected flange.
② The working temperature of the remote transmission device is determined by the type of filling fluid selected.
③ The influence of medium temperature on remote differential pressure transmitters refers to the output changes caused by the same temperature acting on both sides of the remote transmission device starting from room temperature.
④ The effects of static pressure and temperature were measured at the maximum range.
⑤ The maximum length of the capillary tubes on both sides of the DP type remote differential pressure transmitter is 7.5 meters, with a length difference of 4.5 meters between the two sides.

Flat flange (RFW)Remote differential pressure transmitter

Convex flange type (EFW)Remote differential pressure transmitter

Flat (PFW)Remote differential pressure transmitter

Size Table of Connection Flanges for Remote Transmission Devices (Applicable to ZYRTW, ZY-EFW, and ZY-PFW Models)

Flange specifications
Flange size
Pad ring
Installation size
Insert cylinder
code
orifice
pressure
grade
outside diameter
D
Convex diameter
d
Convex height
f
thickness
diameter
F
aperture
φ
Distribution circle
K
Number of holes
n
diameter
h
diameter
B
Protruding length
L
A
E
0A1
1"
150Lb
108
___
5.5
20
24
66.5
27
79.4
4
15
___
___
0A3
300Lb
124
23
88.9
19
0A6
600Lb
1A1
11/2"
150Lb
127
79
42
98.4
15
1A3
300Lb
156
26
114.3
23
1A6
600Lb
28
2A1
2"
150Lb
152
92
23
92
52
120.6
19
Temporary supply
60
50 (2")
100(4")
150(6")
2A3
300Lb
165
26
127
8
2A6
600Lb
31
3A1
3"
150Lb
191
127
27.5
127
79
152.4
4
19
77
3A3
300Lb
210
32.5
168.3
8
23
3A6
600Lb
37.5
4A1
4"
150Lb
229
157
28
157
103
190.5
19
95
4A3
300Lb
254
33.5
200
23
4A6
600Lb
273
43.5
216
25

Threaded Installation (RTW)differential pressure transmitter

Sanitary (SSW)Remote differential pressure transmitter

Remote differential pressure transmittermodel selection

Remote transmission transmitter is a variant product that adds a remote transmission device to the transmitter body, so its selection work can be carried out in two steps: first, determine the type (DP), measurement range, and structural materials of the transmitter body, and then determine the type and size of the remote transmission device according to the installation requirements on site. Due to the close relationship between the various parameters that make up the filling system (such as the working temperature, viscosity, and capillary length of the filling fluid) and the performance indicators of the transmitter, they are included in the selection category of the transmitter body and are not separately listed for selection.

★ ZY3051LP typeRemote differential pressure transmitter

Code measurement range (KPa)
3
4
5
6
7
8
0 - 1.3
0 - 6.2
0 - 31.1
0 - 117
0 - 345
0 - 1170
~ 7.5
~ 37.4
~ 186.8
~ 689.5
~ 2068
~ 6895
Note: When selecting range code 3, a flange with a diameter of 4 "must be used.
2. The remote transmission devices PFW, EFW, RTW, and SSW can choose range codes 3, 4, 5, and 6.
3. The remote transmission device RFW can choose range codes 7 and 8.

Code output format
SF
S
4~20mA. DC digital amplifier with square root output and 4-digit digital display
4~20mA. DC intelligent amplifier and uses HART protocol communication

Code capacity and joint material, isolation membrane material
12 carbon steel 316 steel
22 316 steel 316 steel
Note: Generally, code 12 is selected, and code 22 is selected in humid and corrosive environments.

Code: Type of filling fluid
Low viscosity silicone oil -60-150 ℃ ρ=0.93
S ordinary silicone oil -45~205 ℃ ρ=0.96
High temperature silicone oil -10~300 ℃ ρ=1.07
N vegetable oil -15~200 ℃ ρ=0.92
Distilled water+5~70 ℃ ρ=1.0
Note: The codes N and W are used in situations with strict hygiene requirements and can be used
Avoid contamination of process media caused by leakage of filling fluid.
Code capillary length (m)
00 without capillary tube
03 1.0(3ft)
05 1.5(5ft)
10 3.0(10ft)
15 4.5(15ft)
20 6.0(20ft)
25 7.5(25ft)
Note: 1. The long capillary tubes on both sides are represented by two digits.
2. The unequal length of the thin tubes on both sides is represented by four digits, with the first two digits indicating the length of the high-pressure side; The last two digits indicate the length of the low-voltage side.
3. The length difference of the long capillary tube is ≤ 4.5 meters.
4. "00" represents the capillary tube on this side, which uses a general pressure guiding tube to balance the static pressure.
Code selection parts
M3 digital indicator with 4-digit LCD digital display
B1 pipe bending bracket (installation pipe diameter 60)
B2 board bending bracket
B3 pipe installation flat bracket (installation pipe diameter 60)
D explosion-proof type, explosion-proof mark Exd Ⅱ BT4-6
I intrinsic safety type, explosion-proof mark Exia Ⅱ CT5

ZY3051LP 4S 12 H 05 20 M3 B3 d-171.12~6.12KPa Selection Example

★ ZY3051LP flat flange remote transmission device

Code washing spare hole
11 None
21 has
Note: When the flange diameter is less than 2 ", a gasket ring is required. When the flange diameter is greater than or equal to 2", a gasket ring is only required if there is a flushing hole.

Code: Remote Transmission Diaphragm Material
316L steel
B Hastelloy C
Tantalum C
N Nickel 20
V Monel alloy
H Titanium

Code installation flange diameter

2 2"
3 3"
4 4"
Note: When using range code 3, a diameter of 4 "must be used.

Code Installation Flange Standard
ANSI and HG20615

Code installation flange pressure rating
1 150Lb or PN10/16bar
3 300Lb or PN25/40bar
6 600Lb or PN64bar
Note: Refers to the pressure rating for installing accessory flange covers.

Code: gasket ring, flange cover, diaphragm seat
A
B
E
316 steel
Hastelloy C
316 steel
304 steel
304 steel
carbon steel
316 steel
316 steel
316 steel
Note: Structural material code B, equipped with remote transmission diaphragms other than 316L steel.

ZY3051LP 21 A 4 A 3 E Selection Example

★ ZY3051LP thread mounted remote transmission device

Code flushing hole
11 None
12 has

Code: Remote Transmission Diaphragm Material
316L steel
B Hastelloy C
Tantalum C

Code: Installation flange material, sealing gasket material, membrane sheet seat material
11
31
carbon steel
304 steel
PTFE
PTFE
316 steel
316 steel
Note: The structural material code 31 is equipped with remote transmission diaphragms other than 316L steel.

Code: Liquid receiving cover
A
B
E
316 steel
Hastelloy C
carbon steel
Note: The material code for the liquid receiving cover is B, and it is equipped with a remote transmission diaphragm other than 316L steel.

Code pressure screw hole
11
12
13
14
15
17

NPT
NPT
NPT
NPT
NPT 1
NPT 1(At this time, there is no flushing hole)

ZY3051LP11 A 31 A 15 Selection Example

★ ZY3051LP Sanitary Remote Transmission Device

Code insertion tube
31 diameter 3 "(Φ 70), pressure rating 150LB (2MPa)
33 diameter 3 "(Φ 70), pressure rating 300LB (5MPa)

Code: Remote Transmission Diaphragm Material: Insertion Tube Material: Clamp Material
A
B
316L steel
Hastelloy C
316 steel
316 steel

carbon steel
304 steel

Code protrusion length (mm)
2
4
6
50(2")
100(4")
150(6")

Code installation attachment
N
Y1
Y2
without
With clamps
Equipped with clamps and installation cans
Note: Codes N and Y1 are used for spare parts supply, while code Y2 is used for new equipment installation.

sellafterclothesaffairbearNuo

Through the various products sold by our company, we guarantee to provide sales of products and spare parts at the same price within two years,And provide corresponding technical support free of charge according to the requirements of the demander.
Our company is responsible for free maintenance and technical support, as well as skill training for the customer's employees, in case of any quality issues with the products provided within one year (excluding vulnerable parts or accessories).
Due to quality issues with the products provided by our company, it has been verified by our technical department,The company will dispatch professional technical personnel to the site to handle the problem to customer satisfaction (domestic)72Hours, Jiangsu, Zhejiang, Shanghai48Arrive at the scene within hours),Technical support is available6Respond within hours.

If you are correctZY3051LP Double Flange Liquid Level TransmitterIf you are interested and would like to learn more detailed product information, please fill out the following form to directly contact the manufacturer:
Comments Box
Products of interest: *
Your organization: *
Your name: *
contact number: *
Detailed address:
Common email:
Any of your requests, opinions, or suggestions:
*
Verification Code: * Please enter the result (Arabic numerals), for example: Three plus four=7





Online inquiry
  • Contacts
  • Company
  • Telephone
  • Email
  • WeChat
  • Verification Code
  • Message Content

Successful operation!

Successful operation!

Successful operation!