1.overview
DTS6111 three-phase four wire、DSS6111 three-phase three wireThe three-phase electronic energy meter adopts integrated circuits,16positionA/DConversion, digital multiplier, application of digital sampling processing technology andSMTProcess, instruments designed and manufactured based on the actual electricity consumption of industrial users. This meter uses an independent three unit metering module to measure the active energy of three-phase forward and reverse directions. Measurement errors have stability.
Main features: It has good resistance to electromagnetic interference, low self consumption, high accuracy, anti-theft, wide range, long service life, and can be used to display liquid level.
This meter is suitable for an ambient temperature of -10~50℃, relative humidity not exceeding 85%.
2.function and characteristic
1It has the function of bidirectional measurement of active energy, and the LCD display shows the total amount of electricity;
2HavingRS-485And infrared communication, which can remotely and conveniently read the total power of the energy meter;
3Can set or retrieve parameters such as total power consumption, instrument constant, meter address, meter password, etc;
4Equipped with a programming switch, it can be programmed online;
5The chip has a watchdog system inside, which ensures data security and reliability, and can store power outage data for a long time (continuous power outages can be stored for more than 10 years);
6Isolated power sources, namelyCPUMeasurement section andRS485The interface provides reliable working power supply.
7It has a phase failure indication function.
8Communication protocol
According to the Communication Protocol for Multi functional Energy MetersMulti-function watt-hour meter communication protocol》DL/T 645—2007The standards of the power industry in the People's Republic of China shall be implemented.
3.Working principle
DTS6111 three-phase four wire、 The working principle of DSS6111 three-phase three wire type three-phase static energy meter is shown in Figure 1.
This electric energy meter adopts a three-phase power supply mode and can work normally under any single-phase power supply situation.
When the electric energy meter is working, the voltage and current are sampled separately by the sampling circuit and sent to the large-scale dedicated integrated circuit for buffering and amplification. Then, they are converted into digital signals by a 16 bit A/D converter, processed by a digital multiplier, and sent to the CPU for processing. Finally, the CPU sends the processed data to the display section, step counter, and other output units as needed.
4.Specifications, models, and technical indicators
4.1Specification and model
|
model |
accuracy Level |
reference voltage Un |
Rated current Ib |
Access method |
instrument constant imp/kWh |
|
DTS6111 DSS6111 |
0.5, one |
3X220/380 3X57.7/100 |
1.5(6) |
Mutual inductance type |
1600 |
|
10(40) |
direct-type |
400 |
|||
|
15(60) |
direct-type |
400 |
|||
|
20(80) |
direct-type |
160 |
4.2Basic Error (Balance Load Error Limit)
|
current |
Power factor (COS) |
Basic error (%) |
|
|
0.5 |
1 |
||
|
0.01Ib≦I<0.05Ib |
1.0 |
±1.0 |
|
|
0.02Ib≦I<0.05Ib |
1.0 |
|
±1.5 |
|
0.05Ib≦I<>< span=''><> |
1.0 |
±0.5 |
±1.0 |
|
0.02Ib≦I<0.1Ib |
0.5(Sensory) |
±1.0 |
|
|
0.02Ib≦I<0.1Ib |
0.8(Capacity) |
±1.0 |
|
|
0.05Ib≦I<0.1Ib |
0.5(Sensory) |
|
±1.5 |
|
0.05Ib≦I<0.1Ib |
0.8(Capacity) |
|
±1.5 |
|
0.1Ib≦I<>< span=''><> |
0.5(Sensory) |
±0.6 |
±1.0 |
|
0.1Ib≦I<>< span=''><> |
0.8(Capacity) |
±0.6 |
±1.0 |
Note: (Ib rated current Imax maximum current)
4.3start
Under the conditions of reference voltage, reference frequency, and COS φ=1.0, the instrument should be able to continuously measure electricity with a load current of 0.001Ib (0.5 level) and 0.002Ib (1 level).
4.4shunt running
When the rated voltage of the voltage circuit is 115% and there is no current in the current circuit, the test output of the instrument should not generate more than one pulse.
4.5Voltage range
Normal operating voltage: 0.9Un-1.1Un
Maximum operating voltage: 0.8Un-1.15Un
4.6power consumption
Voltage line power consumption: ≤ 2W and 5VA
Current line power consumption: ≤ 1VA
4.7Climatic conditions
Normal operating temperature: -10 ℃+45 ℃ Extreme operating temperature: -20 ℃+55 ℃
Storage and transportation temperature: -25 ℃+70 ℃. The humidity can reach 95% for 30 days of the year (naturally diffused), and sometimes up to 85% for the rest of the time.
4.8Mechanical dimensions
Dimensions: 228mm × 144mm × 72mm
4.9Weight:About 1.2kg
5.Installation and wiring
5.1The electricity meter has been inspected and approved before leaving the factory, and is sealed with a lead seal. If there is no lead seal or if it has been stored for too long, relevant departments should be asked to recheck and seal it before installation and use.
5.2The upper part of the electric meter has hook screw holes, which are fixed with M4 hook screws. The lower part of the electric meter has 2 mounting holes, which are fixed to the terminal block with M4X10 or M4X12 ordinary screws. The installation and dimensions of the electric energy meter are shown in the diagram below:
5.3The electricity meter should be wired correctly according to the wiring diagram attached on the back of the terminal box cover, and the wiring screws should be tightened.
5.3.1Functional terminal wiring: (Figure 4.1)

SHAPE \\* MERGEFORMAT
5.3.2Power terminal wiring diagram
DTS6607Three phase four wire direct wiring diagram (Figure 4.2)
DSS6607Three phase four wire current transformer wiring diagram (Figure 4.3)

DSS6607Type Three Phase Three Wire Direct Wiring Diagram (Figure 4.3)

DSS6607Type Three Phase Three Wire Voltage and Current Transformer Wiring Diagram (Figure 4.4)
6.Transportation and storage
The product should not be subjected to severe impact during transportation and unpacking, and should be transported and stored in accordance with GB/T15464-1995 "General Technical Conditions for Packaging of Instruments and Meters".
Inventory and storage should be stored on racks in their original packaging conditions, with a stacking height not exceeding 5 layers.
The storage location should be clean, with an ambient temperature of 0-40 ℃, a relative humidity not exceeding 85%, and no harmful substances in the air that can cause corrosion.
7.Warranty
From the date of manufacture, if the electric energy meter does not meet the requirements specified in the technical specifications, provided that the user complies with the instructions and the manufacturer's lead seal is still intact, the company will provide a one-year return, three-year replacement, and five-year repair guarantee.
Appendix:
Data identification
|
Data Name |
Identifier |
data format |
Length |
Read and write characteristics |
|
Current active total electrical energy |
9010 |
XXXXXX.XX |
4 |
read only |
|
Current battery data block |
901F |
|
20 |
read only |
|
Electric meter constant |
C030 |
NNNNNN |
3 |
read only |
|
Electricity meter number |
C032 |
NN……..NN |
6 |
Reading and writing |
|
Password permissions and passwords |
C212 |
NNNNNNNN |
4 |
write |
|
*Freeze active electrical energy |
9A10 |
XXXXXX.XX |
4 |
read only |
|
Total energy floor |
C119 |
NNNNNN.NN |
4 |
write |
|
Reverse active total electrical energy |
9020 |
NNNNNN.NN |
4 |
read only |
|
*Power interruption and transmissioncontrol |
C028 |
NNNN |
2 |
write |
|
Electricity meter operation status word |
C020 |
status word |
1 |
read only |