DC0-20mAUser Manual for Analog Data Acquisition Module
XY885-AII8
Brief introduction
Imported16Bit analog-to-digital conversion chip, convert8roadDC0-20mAsimulateThe signal is converted into a digital signal throughRS485Interface output,DC0-20mAEnter the corresponding numerical value as0-20000The highest measurable valueDC24mA.DC0-20mAAnalog signal input and working power supplyRS485Isolation between them.RS485Communication adopts standardsmodbus-rtuProtocol, compatible with various configuration software,PLCTouch screen networking. leave the factoryPresetsRS485Communication parameters: module address1, baud rate9600,8One data bit, no checksum,1Stop position, users can modify communication parameters through the upper computer parameter setting software.
2、 Main technical indicators
model |
XY885-AII8 |
Input signal |
8roadDC0-20mAperhapsDC±20mA |
measurement accuracy |
0.2% |
Input isolation |
Input signal and working power supplyRS485Isolation between outputs, isolation voltage≥1500VDC |
Sampling rate |
16order/In seconds,8Channel cycle measurement |
communication interface |
RS485 |
communication protocol |
Modbus-rtu |
Baud rate |
2400,4800,9600,19200,38400,57600,115200 |
Parity bit |
No verification, odd verification, even verification |
Power communication indicator light |
After power on, the indicator light stays on and flashes once upon receiving a command frame |
Working power supply |
DC9-36V |
Installation method |
35mmDIN-Rail Mounting |
External dimensions |
131X72X27mm |
IIIRS485communication
3.1 RS485communication
Communication baud rate:2400、4800、9600、19200、38400、57600、115200, factory preset values9600;Parity bits: no parity, odd parity, even parity, factory default value without parity;8One data bit. standardmodbus-rtuProtocol, Instrument Address:1~247, factory preset values1Communication baud rate,The parity bit and communication address are set through the upper computer parameter setting software.
support03H、04HRead command,03H、04HThe function of reading commands is the same;06H、10HWrite commands.
Message format description:
command03H(perhaps04H): Read command
Host request: address+command+data address+Length+ CRCCheck Code
1byte + 1byte + 2byte + 2byte + 2byte
Address: For the module address to be queried, it can be found at1~247Internal settings, occupying 1One byte
Command:03H(perhaps04H)Read command, length is 1One byte
Data address: The starting address of the read data, occupying 2One byte
Data length: The length of the read data word
CRC16Verification code: Low8Located in the front, high8Located at the back, occupying2One byte
Module response:address+command+Length+Data information+ CRCCheck Code
1byte + 1byte + 1byte + nbyte + 2byte
Address: In response to the instrument address code, the length is 1One byte
Command:03H(perhaps04H)The length is 1One byte
Data length: The byte length of the read data
Data information: Read data
CRC16Verification code: occupied2One byte, low8Located in the front, high8Located at the back
3.2 Example of Communication Messages
Read data register(function code03H/04H): Read out8roadDC0-20mAMeasurement value,1~8The input values of the road current are2.000mA、4.000mA、4.505mA、8.756mA、10.337mA、12.000mA、15.006mA、20.000mAThe instrument address is1.
Host reads data frames(Data to16Binary format representation):
address |
command |
start address(MSB first) |
Number of registers(MSB first) |
Check Code(Little Endian) |
01 |
03 |
00,00 |
00,08 |
44,0C |
Module responds to data frames(Data to16Binary format representation):
address |
command |
Length |
data segment(16byte) |
Check Code |
01 |
03 |
10 |
07, D0,0F,A0,11,99,22,34,28,61,2E,E0,3A,9E,4E,20 |
7D, F4 |