The smoke concentration monitor uses the principle of laser backscatter testing to measure the smoke concentration of the tested flue gas. The embedded high stability laser signal source of the smoke concentration monitor passes through the flue and irradiates smoke particles. The irradiated smoke particles will reflect the laser signal, and the reflected signal intensity will change proportionally to the smoke concentration. The smoke concentration monitor detects the weak laser signal reflected by smoke and can calculate the concentration of smoke and dust in the flue through specific algorithms.
project |
Specifications |
working principle |
Laser backscatter measurement |
Measurement object |
Industrial waste gas, smoke and dust |
mechanical properties |
Shell: All metal shell Dimensions: (W × H × D) 160mm × 185mm × 160mm Weight: 2 Kg
Protection level: IP66
|
optical properties |
Working wavelength: (650 ± 20) nm |
Measurement performance |
Measurement range: (0~100500100020004000) mg/m3, adjustable zero drift: ± 2% F? S
/24-hour range drift: ± 2% F? S/24-hour indication error: ± 2% F? S Response time: ≤ 10s Flue gas
Diameter: (0.7-20) m
|
Power requirements |
DC 24V/0.3A |
Environmental working conditions |
Working temperature: -20oC~+50oC |
interface characteristics |
Analog output: (4-20) mA
Digital interface: RS485
1 relay output: Over limit alarm indication (limited to LSS2004-A type)
Relay rating: 2A 30VDC
4-channel analog input: can integrate temperature, pressure, flow and other parameters, and convert them into digital output
|