Detailed information on RH-8519 wall mounted phosgene (COCL2) detection alarm:
RH-8519 wall mounted phosgene (COCL2) detection alarmProduct Overview:
The RH-8519 series single point wall mounted phosgene detection alarm is an instrument that can continuously detect the concentration of phosgene in the working environment. It can be widely used in various on-site environments such as factories, offices, and warehouses to monitor the concentration of phosgene online. This phosgene detection alarm adopts a natural diffusion gas detection method, and the sensitive element adopts an imported electrochemical sensor from Membrapor, Switzerland, which has high sensitivity and excellent repeatability; High brightness LED backlight and LCD display screen display the concentration value of leaked gas in real time. If it exceeds the preset alarm point, the sound and light alarm signal and relay control signal will be immediately activated; The international standard 4-20mA signal can be directly connected to the factory DCS system, and the RS485 digital signal can be connected to the factory upper computer.
RH-8519 wall mounted phosgene (COCL2) detection alarmProduct features:
Imported electrochemical sensors with stable and reliable performance;
Provide LCD display and sound and light alarm, with complete functions;
Intelligent design, zero adjustment, alarm setting, and calibration are very convenient;
Two alarm relays can output control signals to drive equipment such as fans;
The instrument is powered by a wide range of DC9-24V (AC220V can be directly used with a power adapter), and can be used by connecting the power supply;
Metal shell, sturdy and reliable;
Infrared remote control makes it easier to set and modify instrument parameters;
Equipped with standard 4-20mA current signal and RS485 digital signal output.
Application areas:
Dyes, papermaking, pharmaceuticals, medical, food, anti-corrosion, disinfection, fertilizers, resins, adhesives and pesticides, raw materials, samples, production processes and breeding plants, waste disposal plants, hair perm sites, production workshops and living places
RH-8519Technical parameters:
Input power supply: 9-24VDC
Current consumption: 20-200mA
Detection principle: electrochemistry
Display mode: LCD display screen
Detection method: diffusion type
Alarm mode: Level 2 sound and light alarm
Detection range: 0-50PPM or custom
Alarm error: ≤± 5% alarm set value
Accuracy: ± 5% FS
Working temperature:- 20℃-45℃
Resolution: optional
Working humidity: 15-90% RH (non condensing)
Preheating time: 1 Min
Pressure range: Atmospheric pressure
Signal output: 4-20mA or RS485
Service life: 2 years (in air)
Contact capacity: 1A/120VAC or 1A/24VDC
Zero drift: ≤ ±2%FS/6h
Repeatability: ≤ ±2%FS
Span drift: ≤ ±5%FS/6h