1、 Product Overview
DC24V or AC220V power supply provides isolated distribution power for on-site transmitters, while realizing the conversion of various signals such as voltage, current, mV, etc.
Input terminal interface current source, universal for two-wire and three wire transmitters; Internally, efficient magneto electric isolation technology is used to isolate the input, output, and power supply from each other, with characteristics such as high precision, high linearity, and low temperature drift.
1、 Model meaning
2、 Product selection
▲SNDP-IPXXX
Example: SNDP-IP111, Current input, one in one out, both input and output are 4-20mA
▲SNDP-UXXX
Example: SNDP-U141, Voltage input, one in one out, input 0-75mV, output 4-20mA
3、 Technical parameters
▲ Input terminal
Input signal: 4-20mA; 0-20mA; 0-75mV,0-5V; 0-10V, etc
Distribution voltage: 24V (maximum driving current 30mA)
Input impedance: Current input: ≤ 50Ω;
Voltage input: ≥ 300KQ
▲ Output terminal
Output signal: 4-20mA; 0-20mA; 0-5V; 0-10V
Output load resistance: RLs500 Ω (when outputting as a current signal)
RL210KQ (when outputting as a voltage signal)
▲ Basic parameters
Power supply: DC24V ± 10% or AC85-265V
Current consumption: ≤ 50mA (one in one out, 24V power supply, distribution input, 20mA output)
≤ 70mA (one in two out, 24V power supply, distribution input, 20mA output)
≤ 100mA (two in two out, 24V power supply, distribution input, 20mA output)
Basic accuracy: 0.1% F.S
Temperature drift: 0.005% F.S./C (-20 ℃~+55 ℃)
Response time: ≤ 10mS(0-90%)(TYP)
Insulation strength: 1500VAC/1min (between input, output, and power supply)
Insulation resistance: ≥ 100MQ (between input, output, and power supply)
Working temperature range:- 20℃~+55℃
Electromagnetic compatibility: Complies with GB/T18268 (IEC61326-1)
Applicable on-site equipment: two-wire and three wire transmitters; Current source, voltage source
Dimensions and wiring diagram