Power transmitter SINEAX P530/Q531
▶Product Introduction
SINEAX P530/Q531 power transmitter is used to measure the active power/reactive power of single-phase AC current or three-phase current.
▶Product Features
▪Monitor power consumption in energy distribution systems and process engineering
▪Determine the time sequence of power input
▪Avoid underload and overload situations, load control
▪Monitoring rotating machinery
▪Monitoring blockage, for example, in conveying equipment
▪Monitor energy distribution
▪The output signal can be used for indication, registration, monitoring, and control
▪Ensure safety through current isolation and shockproof terminals (IP20)
▪Germanischer Lloyd standards, applicable to ships
▶technical data
▪Measurement input: single-phase AC current, 3-wire three-phase current with balanced/unbalanced load or 4-wire three-phase current with balanced (P530 only)/unbalanced load
▪Nominal voltage Un 100... 115V, 200... 230V, 380... 440V, 600... 690V or 100... 690V
▪Nominal current In 1A, 5A or user-defined (1... 6A)
▪The maximum measurement range is ≥ 0.75 to 1.3
▪Nominal output, unipolar or bipolar
▪Nominal frequency 50/60Hz, sine wave
▪Measurement range: P530: Maximum value ≤ 0.75 to 1.3 · nominal output, unipolar or bipolar Q531: maximum value ≤ 0.5 to 1.0 · nominal output, unipolar or bipolar
▪Measurement output: maximum output value 1mA, 2.5mA, 5mA, 10mA, 20mA, 10V or user-defined 1... 20mA or 1... 10V, output signal unipolar, bipolar or zero crossing, set time<300ms
▪Measurement principle: TDM method
▪Accuracy: Level 0.5 within 15... 30 ℃
▪Power supply: 24-60V AC/DC or 85-230V AC/DC, ≥ 85-230V AC from measurement input or 24V AC/24-60V DC, connected through the low voltage side
▪External dimensions: 69.1x70x112.5mm (single-phase), 69.1x105x112.5mm (3/4 line three-phase current)
▶Standing type