The multi-channel gas alarm device continuously monitors the ambient air and provides early alarms for hazardous, explosive, non flammable gases and vapors.
| technical parameter|
Sensor: |
Semiconductor sensors, catalytic combustion sensors Thermal conductivity sensor, electrochemical sensor infrared sensor |
Sensor input: |
6 two-wire sensors (such as 592 TOX) or 3 three wire sensors (such as GTR 196) or 2 three wire sensors+4 two-wire sensors |
Sensor power supply: |
19 V =/500 mA |
Range: |
CO 0- 300 ppm NO2 0- 30 ppm CH4 0- 100 % LEL CO2 0- 10 VOL% Other ranges can be provided as needed |
Accuracy: |
< 3 %, f.s.d. |
Environmental temperature: |
-10 . . . + 40°C |
Temperature impact: |
<3% within ± 20'C range |
Set time (t)90): |
< 60 s |
Installation: |
Wall assembly |
|
Security level:IP 54 |
Output signal: |
Voltage output, 1-5V RS232 interface 3 alarm signal relays 1. Fault relay |
Relay capacity: |
230V,450VA Other voltages can be provided as needed |
Voltage: |
230 V, 50 Hz 115 V, 60 Hz (optional) 24 V=(optional) |
Power: |
14VA |
Size (WxHxD): | 225x 180 x 105 mm |
Weight: |
About 1.5KG |
Gas | Molecular formula |
Range of measurement |
carbon monoxide | CO | 0-300ppm |
Methane (natural gas) | CH4 | 0-100% LEL or 100% Vol |
alcohol | C3H8 |
0-100%LEL |
ammonia | NH3 | 0-250ppm |
gasoline | CnHm | 0-100%LEL |
butane | C4H10 | 0-100%LEL |
chloroform | CHCl3 | 0-100%LEL |
Hydrogen chloride | HCL | 0-300ppm |
helium | He | 0-100%Vol |
carbon dioxide | CO2 | 0-5000ppm,0-100% |
nitric oxide | NO | 0-100ppm |
hydrogen | H2 | 0-100% LEL or 100% VoI |
Nitrogen dioxide | NO2 | 0-300ppm |
propane | C3H8 | 0-100%LEL |
oxygen | O2 | 0-25%VoI |
carbon tetrachloride | CCI4 | 0-100ppm |
toluene | C7H8 |
0-1000ppm |
Organic solvents | VOC | 0-100% LEL or 2000ppm |
xylene | C9H10 | 0-100% LEL or 2000ppm |
Other gases and ranges can be adjusted from ppm to 100% as required. Please contact us for details |
features
•Using different measuring sensors
•Ready, error, and gas alarm indicators
•Assisted operation through a 2-key menu
•Built in buzzer
•Optional gas average value every half an hour
•The three alarm limits can be individually adjusted within the testing range of 5-100%
•Three floating alarm outputs drive additional alarm and control systems
•Floating incorrect contact points
•Connect the serial output of a printer or computerRS232
•High reliability
•Low current consumption
•Plastic, wall mounting box
•Easy to operate
Optional accessories
Signal horn, alarm light, alarm slogan, ventilation control, testing
Instruments, plotters.