Oneoverview
Three phase intelligent digital display power instrument is a new generation of three-phase intelligent digital display current and voltage Current voltage combination table,Mainly used for AC voltage in electrical circuits,Real time measurement and indication of current,And through485Interface or analog transmission output interface for remote transmission of measured parameters.High measurement accuracy,Stability,Long term work face calibration,Features such as on-site parameter settings through panel buttons,It is an ideal substitute for the original pointer instrument
IIcharacteristic
This series of products adopts large-scale integrated circuits and high-performance microcontrollers in hardware, discrete digital signal processing technology in software, and modular design in design. Make this product have a high cost-effectiveness.
1The display magnification, display mode, and display brightness can all be set through buttons.
2.mail address Baud rate All settings can be made through buttons
3.Has upper and lower limit alarms,alarm mode,The alarm threshold can be freely set
4.have0~20mA 4~20mASend output immediately Free to set
5.Can be withPLCTouch Screen Waiting for networking
IIISpecification(Execution standardsGB14913-94)
performance |
index |
||
voltage |
RATING |
AC400V |
|
overload |
1.2times Instantaneous:10times |
||
power consumption |
<> |
||
impedance |
5000KΩ |
||
accuracy |
RMSmeasure 0.5level |
||
electric current |
RATING |
AC5A |
|
overload |
sustain1.2times instantaneous10times10S |
||
power consumption |
|||
impedance |
|||
accuracy |
RMSmeasure accuracy 0.5level |
||
Input network |
support3each other3Line,3each other4line |
||
frequency |
50Hz |
||
Display mode |
Three row digital tube Display the entire four digits |
||
power supply |
Working power supply |
AC220Range(85%~115%)Special needs May make to order |
|
power consumption |
less than5VA |
4Usage and precautions
1. Please check carefully before powering on Confirm auxiliary power supply Is the input signal line correct
2. The instrument should not be subjected to collisions and severe vibrations, and the usage environment should meet the requirements
Fiveoperational condition
1.ambient air temperature
1).The upper limit value does not exceed40'c
2)The lower limit shall not be lower than-5'
3).Daily average not exceeding35'c
4).When the ambient temperature exceeds the above range, users can negotiate with our company
5)The altitude of the installation location shall not exceed2000rice
2.atmospheric conditions
Relative humidity of the atmosphere compared to the surrounding air temperature+40‘Cnot more than50%There can be higher humidity at lower temperatures Degree, due to temperature changes Measures must be taken for the condensation sent on the product
VIPackaging and storage
1.Instruments and their accessories should be stored in a ventilated and dry place under packaging conditions to avoid moisture and corrosive gas erosion
2. The maximum storage temperature shall not exceed+70'cnot less than-35'crelative humidity<>
Long term storage without use, please power on every three months,Not less than four hours each time
Long term storage Should avoid direct sunlight
7、 Appearance and installation openings
Instrument code |
Instrument appearance |
External dimensions((mm) |
Dimension |
||||
long |
wide |
deep |
long |
wide |
|||
120 |
120 |
85 |
108 |
108 |
|||
96 |
96 |
85 |
91 |
91 |
|||
80 |
80 |
85 |
76 |
76 |
|||
72 |
72 |
85 |
67 |
67 |
|||
48 |
48 |
85 |
45 |
45 |
|||
48 |
96 |
85 |
91 |
45 |
Panel Description
Panel button instructions
< || ="">Left Used for reducing numbers Or the previous option
||>>Right key Used for increasing numbers Or the next option
Switching between menus of the same level||>>or<||>||>
MenuMenu key Used to enter settings during standby mode Used in the settings for Return without savingPREVIOUS MENU
enter key Used to enter the sub menu or save and returnPREVIOUS MENU
pilot lamp |
describe |
K |
show thousand |
M |
show omen |
V |
Indicates that the current display is voltageV |
A |
Indicates that the current is displayed as currentA |
K+A |
Indicates that the current display is in kiloamperes |
K+V |
Indicates that the current display is in megaamps |
K+V+A |
The current displayed item is apparent power Kilovolt ampereKVA |
K+Wat |
Currently displayed as active power in kilowattsKW |
K+Var |
Currently displayed as reactive power kilovarKvar |
PF |
The current display item is power factor |
Hz |
The current display item is frequency |
J1H |
The first upper limit alarm |
J1L |
First lower limit alarm |
J2H |
Second upper limit alarm |
J2L |
Second lower limit alarm |
Di1 |
The first switch input |
Di2 |
Second switch input |
Single organizational structure
explain:
First row digital display |
Second row digital display |
explanation |
|
display mode |
disp |
A |
Display Current |
V |
Display voltage |
||
L |
Current voltage wheel display |
||
Voltage conversion ratio |
Pt |
Voltage conversion ratio After entering this menu, press>>Number increase pressNumber reduction |
|
current transformation ratio |
Ct |
current transformation ratio After entering this menu, press>>Number increase pressNumber reduction |
|
Connection |
net |
N.3.4 |
Three-phase four-wire |
N.3.3 |
Three phase three wire |
||
brightness |
bled |
brightness |
|
Baud rate |
baud |
1200 |
The baud rate is1200 |
2400 |
The baud rate is2400 |
||
4800 |
The baud rate is4800 |
||
9600 |
The baud rate is9600 |
||
node address |
Sn |
Slave address (1-247) |
|
Transmission mode |
Ao-S |
IaL |
Set as corresponding electrical parameters for instant delivery0~20mA,Set the alarm to correspond to a low electrical parameter alarm example1 Ao-SSet asIaLThen I will send it to youAPhase current0~20mA Just send it, |
alarm mode |
o1-S |
IbL |
|
o2-S |
IcL |
||
UaL |
|||
UbL |
|||
UcL |
|||
IaH |
Set the transmission to the corresponding electrical parameters4~20mA,Alarm set to correspond to high electrical parameter alarm example1 Ao-SSet asIaHThen I will send it to youAPhase current4~20mA Just send it, |
||
IbH |
|||
IcH |
|||
UaH |
|||
UbH |
|||
UcH |
|||
o1-V |
After entering this menu, the second row displays the alarm value. The alarm value is=threshold/Nominal value ×1000 |
||
O2-V |
|||
Debg |
Factory mode, used for engineering debugging and testing |
||
Save |
ENTER Later appearedYes NoPress Enter again Save settings and exit, pressMenuEXIT WITHOUT SAVING |
Connection
Note: If attached communication call the police Analog transmission output Waiting for functions Wiring diagram Please refer to the wiring sticker of the instrument itself
Warranty period:From the date of manufacture, if this instrument is damaged under non-human conditions in accordance with the requirements specified in the user manual, the company will provide compensation1year warranty
Ordering Instructions:When placing an order, the complete instrument model should be specified in the contract
for example
year the moon sun
Contact Number
Serial Number |
name |
External dimensions |
transformation ratio |
communication |
call the police |
Transducer |
Other requirements |
quantity |
1 |
3Phase current meter |
72x72 |
100/5 |
√ |
2road |
15 |
||
2 |
3Phase current meter |
96x96 |
80/5 |
√ |
1road |
10 |
||
Communication instructions:
ModbusIt is fromModicon(Now a brand of Schneider Electric)1979Invented in [year], it is the world's first bus truly used in industrial fieldsagreement.
ModbusHas the following characteristics:
(1)Standard and open, users can use it for free and with confidenceModbusagreementThere is no need to pay license fees and it will not infringe on intellectual property rights.
(2)ModbusCan support multiple electrical interfaces, such asRS-232、RS-485It can also be transmitted over various media, such as twisted pair cables, fiber optics, wireless, etc.
(3)ModbusThe frame format is simple, compact, and easy to understand. Easy for users to use and simple for manufacturers to develop.
ModbusThere are three branches under the communication protocol:Modbus-tcp Modbus-ascii,Modbus-rtu.
What does our product supportModbus-rtuagreement. The electrical rules areRS485Electrical Rules
Modbus-RTUThe data frame format of the protocol:
The query message structure is as follows:
node address |
function code |
The starting register address is high |
Low starting register address |
High data length |
Low data length |
CRCLow byte |
CRCHigh Byte |
1One byte |
1One byte |
2One byte |
2One byte |
2One byte |
Our product supports function code have
03/04: Used for querying
6: Used to write to a single register
16(Decimal): Hexadecimal is 10 Used for writing multiple registers
The format of the returned data frame is as follows:
node address |
function code |
Length |
Data Content |
CRCL |
CRCH |
1One byte |
1One byte |
Calculated by byte of data content in words |
specific data |
one byte |
one byte |
For example: three-phase current
Address code |
function code |
Starting address high byte |
Low byte starting address |
High byte data length |
Low byte data length |
Low byte checksum |
High byte checksum |
01 |
03 |
00 |
10 |
00 |
03 |
04 |
0E |
return
Address code |
function code |
Length |
Data Content |
Data Content |
CRCL |
CRCH |
01 |
03 |
00 |
06 |
... ... |
Write data frame format
Address code |
function code |
Starting register high |
Start register low |
High byte number of registers |
Low byte number of registers |
Length |
Low address data high byte |
Low address data high byte |
…… |
High address data high byte |
High address data, low byte |
CRCL |
CRCH |
For example, registers Activate the relay1Output a contact signal
Register Address List:
address |
Corresponding internal variables |
describe |
read/write |
data type |
1 |
Disp |
Display mode ① |
R/W |
Uint16 |
2 |
Sn |
Slave address |
R/W |
Uint16 |
3 |
Baud |
Baud rate ② |
R/W |
Uint16 |
4 |
Bled |
brightness |
R/W |
Uint16 |
5 |
Ao-s |
auxiliary word for ordinal numbers1Road analog output mode ③ |
R/W |
Uint16 |
6 |
o1-s |
auxiliary word for ordinal numbers2Road analog output mode ④ |
R/W |
Uint16 |
7 |
o2-s |
auxiliary word for ordinal numbers3Road analog output mode ④ |
R/W |
Uint16 |
8 |
Ao-v |
auxiliary word for ordinal numbers4Road analog output mode |
R/W |
Uint16 |
9 |
o1-V |
auxiliary word for ordinal numbers1Road alarm value |
R/W |
Uint16 |
10 |
o2-V |
auxiliary word for ordinal numbers2Road alarm value |
R/W |
Uint16 |
11 |
Pt |
Voltage conversion ratio |
R/W |
Uint16 |
12 |
Ct |
current transformation ratio |
R/W |
Uint16 |
13 |
Do |
Switching output status |
R |
Uint16 |
14 |
Di |
Switch input status |
R |
Uint16 |
15,16 |
Ia |
APhase current |
R |
IEEE754 Float |
17,18 |
Ib |
BPhase current |
R |
IEEE754 Float |
19,20 |
Ic |
CPhase current |
R |
IEEE754 Float |
21,22 |
Ua |
APhase voltage |
R |
IEEE754 Float |
23,24 |
Ub |
BPhase voltage |
R |
IEEE754 Float |
25,26 |
Uc |
CPhase voltage |
R |
IEEE754 Float |
① The instrument settings corresponding to the numbers returned by the display mode
0: Display voltage
1:ADisplay Current
2:LWheel display
② Return data Corresponding instrument baud rate
0:1200 bps
1:2400 bps
2:4800 bps
3:9600bps
③ Return the analog output mode corresponding to the data, as well as the alarm
Return data |
Corresponding instrument settings |
describe |
|
0 |
IaL |
answerAPhase electrorheological transmission, 0~20mA |
|
1 |
IbL |
answerAPhase electrorheological transmission, 0~20mA |
|
2 |
IcL |
answerAPhase electrorheological transmission, 0~20mA |
|
3 |
UaL |
answerAPhase voltage transmission, 0~20mA |
|
4 |
UbL |
answerBPhase voltage transmission, 0~20mA |
|
5 |
UcL |
answerCPhase voltage transmission, 0~20mA |
|
6 |
IaH |
answerAPhase electrorheological transmission, 4~20mA |
|
7 |
IbH |
answerBPhase electrorheological transmission, 4~20mA |
|
8 |
IcH |
answerCPhase electrorheological transmission4~20mA |
|
9 |
UaH |
answerAPhase voltage transmission4~20mA |
|
10 |
UbH |
answerbPhase voltage transmission4~20mA |
|
11 |
UcH |
answercPhase voltage transmission4~20mA |
④
Return data |
Corresponding instrument settings |
describe |
|
0 |
IaL |
answerAPhase current lower limit alarm |
|
1 |
IbL |
answerBPhase current lower limit alarm |
|
2 |
IcL |
answerCPhase current lower limit alarm |
|
3 |
UaL |
answerALower limit alarm of phase voltage |
|
4 |
UbL |
answerBLower limit alarm of phase voltage |
|
5 |
UcL |
answerCLower limit alarm of phase voltage |
|
6 |
IaH |
answerAPhase current lower limit alarm |
|
7 |
IbH |
answerBPhase current lower limit alarm |
|
8 |
IcH |
answerCPhase current lower limit alarm |
|
9 |
UaH |
answerAPhase voltage upper limit alarm |
|
10 |
UbH |
answerBPhase voltage upper limit alarm |
|
11 |
UcH |
answerCPhase voltage upper limit alarm |