1. Characteristics:
- Closed structure, good sealing performance
- Low profile and lightweight
- Before leaving the factory, it undergoes effective leak testing/scanning testing
- Suggested final resistance: 300Pa
2. Product advantages introduction:
The enclosed design prevents internal gaps and side leaks, meeting the strict requirements of clean rooms for air quality. Suitable for laminar or non laminar flow cleanliness from level 10000 to level 10
Indoor. Widely used in hospital operating rooms, laboratories, pharmaceutical industry, microelectronics, film and fiber optic equipment, and food processing plants with high cleanliness requirements.
The standard height of the box is 150mm and the thickness is 175mm. It is easy to transport and install, suitable for various types of ceilings. The standard diameter of the air inlet is 250mm, and the interior can be adjusted for height
A diffuser plate is used to effectively disperse and evenly distribute the airflow.
3. Usage period:
Under rated air flow conditions, a new filter must be replaced after 14-18 months or when the resistance of the filter reaches over 300Pa;
4. Model size and parameters
model | Dimensions mm | Rated air volume | efficiency | Initial resistance (Pa) | material | |||||
(Width x Height x Depth) | (m3/h) | H13 | H14 | H13 | H14 | filter material | partition | sealant | Outer frame | |
Disposable integrated non partition high-efficiency filter | 610×610×152 | 800 |
≧99.95% @0.3μm |
≧99.995% @0.3μm |
≦125 | ≦150 | AGM |
Hot melt Glue line |
polyurethane |
high quality aluminum material |
915×610×152 | 1000 | |||||||||
1220×610×152 | 1500 | |||||||||
610×610×175 | 1000 | |||||||||
915×610×175 | 1200 | |||||||||
1220×610×175 | 1800 |