Gas monitoring alarm - MWS 903, multi-channel gas alarm device continuously monitors the ambient air and provides early alarms for dangerous, explosive, non flammable gases and vapors.
Measurable gases:
Acetylene (C)2H2)Ether (C)4H10O)Alcohol (z.B.C)2H6O)Ammonia (NH)3)Gasoline (Petroleum spirit), Butane (C)4H10)Chloroform (CHCl)3)Hydrochlorides (HCL), Hydrogen Cyanide (HCN), Carbon Dioxide (CO)2)Carbon monoxide (CO), methane (natural) Qi CH4)Neon (Ne), Propane (C)3H8)Oxygen (0)2)Tetrachloride Carbon (CCl)4)Toluene (C)7H8)Hydrogen (H)2)Xylene (C)9H10).
Measuring components | range | Measuring components | range |
Carbon monoxide (CO) | 0-300ppm | Nitric oxide (NO) | 0-100ppm |
Methane (CH)4) | 0-100% LEL or 100% VOL | Hydrogen (H)2) |
0-100% LEL or 100% VOL |
Alcohol (C3H8) | 0-100%LEL | Nitrogen dioxide (NO)2) | 0-300ppm |
Ammonia (NH)3) |
0-250ppm | Propane (C3H8) | 0-100%LEL |
Gasoline (CnHm) | 0-100%LEL | Oxygen (O)2) | 0-25%VOL |
Butane (C4H10) | 0-100%LEL | Carbon tetrachloride (CCl)4) | 0-100ppm |
Chloroform (CHCl)3) | 0-100%LEL | Toluene (C)7H8) | 0-1000ppm |
Hydrogen chloride (Hcl) | 0-300ppm | Organic solvents (VOC) | 0-100% LEL or 2000ppm |
Helium (He) | 0-100%VOL | Xylene (C)9H10) | 0-100% LEL or 2000ppm |
Carbon dioxide (CO)2) | 0-5000ppm,0-100% |
Note: Other gases and ranges can be adjusted from ppm to 10% as required, Please feel free to contact us for specific inquiries. |
Sensor input: | 8 two-wire or three wire sensors (such as LCTR 903) 4-20mA current |
Sensor power supply: |
24 V = / 1A |
Range: | CO 0- 300ppm NO20- 30ppm CH40- 100%LEL CO20- 10VOL% Other ranges can be provided as needed. |
Signal input: | 1 input is used to cancel the alarm |
Environmental temperature: |
|
- 10~ +
Output signal: |
Up to 12 alarms 1 alarm relay 1 faulty relay 1 alarm slogan relay All outputs have floating conversion contacts, with a maximum capacity of 250V/4A |
Standard output signal: | Analog output 4-20mA serial interface RS232 |
Main power supply |
230 V, 50 Hz 115 V, 60 Hz (optional) |
Protection level: | IP54 according to DIN40050 |
Size: |
|
240(W)x 160(H)x
Weight: | About 4 kg |
Testing standards: | German technology VDI2053 |
● Clear 4-line LCD display with actual measurement values, half-hour average values, and error messages, operated with a 6-key keyboard
● Ready, fault, and gas alarm indicators
● Assisted operation through a menu of 6 keys
The two alarm limits can be adjusted separately within the testing range of 5-100%
12 floating alarm outputs drive additional alarm and control systems
● Floating faults, alarm device contacts
● Serial output RS232 for connecting to a printer or computer
● High reliability
Low current consumption
Plastic, wall mounting box
● Easy to operate
● Can use UPS power supply
● Optional accessories:
Signal horn, alarm light, alarm slogan, ventilation control, testing instrument, plotter, independent UPS 200-24V power supply.
Other accessories are ordered according to the ordering system.